Change
Water utility · Iowa City · Iowa

University Water System

No open health-based violations on EPA record in the last 10 years; latest legal-limit breach in the period starting April 2017.

Serves about 26,684 people (95 connections) with surface water from its own intake.

  • PWSID IA5225101
  • EPA registered name: UNIVERSITY WATER SYSTEM
  • EPA record checked June 17, 2026
Contact

Contact University Water System

From EPA's record for IA5225101. PurityMap is independent of University Water System.

Mailing address
ATTN WATER PLANT MANAGER, JIM ZARUBA, UNIV WATER PLT 208 W BURLINGTON
IOWA CITY, IA 52242
Directions ↗

Are you this utility? Correct this listing →

EPA compliance record

What EPA's record shows

2 health-based violations in the last 10 years, from EPA's SDWIS compliance database.

  • Total trihalomethanes (TTHM), a by-product of disinfecting water with chlorine, were above the legal limit in 2 quarters since January 2017.
Recent health-based violations for University Water System (PWSID IA5225101)
PeriodContaminantMeasuredLegal limitEPA status
Apr–Jun 2017Total trihalomethanes (TTHM)0.091 mg/L0.080 mg/LResolved
Jan–Mar 2017Total trihalomethanes (TTHM)0.095 mg/L0.080 mg/LResolved
  • Lead: the 90th-percentile result in the latest lead and copper round (the round ending December 31, 2024) was not detected. The federal action level is 15 µg/L, a trigger for more treatment steps, not a legal limit.
  • Missed or late tests or reports: 4 in 10 years.
  • EPA lists 26 enforcement actions in 10 years; the latest on July 1, 2020.
Lab results EPA required (UCMR 5)

1 of 30 contaminants detected in EPA testing

EPA required this system to test for 30 unregulated and emerging contaminants, from January 2024 to October 2024.

  • LithiumAbove the referenced health-based guidance value
    10 µg/L EPA health reference level · not a legal limit
    72µg/L
Results as a table30 results with limit, status, sample date and source
EPA-required lab results (UCMR 5) for University Water System (PWSID IA5225101), Iowa
ContaminantResultLimitStatusSampledSource
Lithium72 µg/L10 µg/L EPA health reference level (screening, not a legal limit)Screening level, not a legal limitAbove the referenced health-based guidance value2024-01-19 to 2024-10-31UCMR5 Analytical Results: UNIVERSITY WATER SYSTEM (IA5225101)
11-Chloroeicosafluoro-3-oxaundecane-1-sulfonic acid (11Cl-PF3OUdS)< 5 ng/LNo federal or state limit; shown for transparencyNot detected above the reporting limit2024-01-19 to 2024-10-31UCMR5 Analytical Results: UNIVERSITY WATER SYSTEM (IA5225101)
1H, 1H, 2H, 2H-perfluorodecane sulfonic acid (8:2 FTS)< 5 ng/LNo federal or state limit; shown for transparencyNot detected above the reporting limit2024-01-19 to 2024-10-31UCMR5 Analytical Results: UNIVERSITY WATER SYSTEM (IA5225101)
1H, 1H, 2H, 2H-perfluorohexane sulfonic acid (4:2 FTS)< 3 ng/LNo federal or state limit; shown for transparencyNot detected above the reporting limit2024-01-19 to 2024-10-31UCMR5 Analytical Results: UNIVERSITY WATER SYSTEM (IA5225101)
1H, 1H, 2H, 2H-perfluorooctane sulfonic acid (6:2 FTS)< 5 ng/LNo federal or state limit; shown for transparencyNot detected above the reporting limit2024-01-19 to 2024-10-31UCMR5 Analytical Results: UNIVERSITY WATER SYSTEM (IA5225101)
4,8-Dioxa-3H-perfluorononanoic acid (ADONA)< 3 ng/LNo federal or state limit; shown for transparencyNot detected above the reporting limit2024-01-19 to 2024-10-31UCMR5 Analytical Results: UNIVERSITY WATER SYSTEM (IA5225101)
9-Chlorohexadecafluoro-3-oxanone-1-sulfonic acid (9Cl-PF3ONS)< 2 ng/LNo federal or state limit; shown for transparencyNot detected above the reporting limit2024-01-19 to 2024-10-31UCMR5 Analytical Results: UNIVERSITY WATER SYSTEM (IA5225101)
Hexafluoropropylene oxide dimer acid (HFPO-DA) (GenX chemicals)< 5 ng/L10 ng/L federal MCL (2024)Not detected above the reporting limit2024-01-19 to 2024-10-31UCMR5 Analytical Results: UNIVERSITY WATER SYSTEM (IA5225101)
N-ethyl perfluorooctanesulfonamidoacetic acid (NEtFOSAA)< 5 ng/LNo federal or state limit; shown for transparencyNot detected above the reporting limit2024-01-19 to 2024-10-31UCMR5 Analytical Results: UNIVERSITY WATER SYSTEM (IA5225101)
N-methyl perfluorooctanesulfonamidoacetic acid (NMeFOSAA)< 6 ng/LNo federal or state limit; shown for transparencyNot detected above the reporting limit2024-01-19 to 2024-10-31UCMR5 Analytical Results: UNIVERSITY WATER SYSTEM (IA5225101)
Nonafluoro-3,6-dioxaheptanoic acid (NFDHA)< 20 ng/LNo federal or state limit; shown for transparencyNot detected above the reporting limit2024-01-19 to 2024-10-31UCMR5 Analytical Results: UNIVERSITY WATER SYSTEM (IA5225101)
Perfluoro (2-ethoxyethane) sulfonic acid (PFEESA)< 3 ng/LNo federal or state limit; shown for transparencyNot detected above the reporting limit2024-01-19 to 2024-10-31UCMR5 Analytical Results: UNIVERSITY WATER SYSTEM (IA5225101)
Perfluoro-3-methoxypropanoic acid (PFMPA)< 4 ng/LNo federal or state limit; shown for transparencyNot detected above the reporting limit2024-01-19 to 2024-10-31UCMR5 Analytical Results: UNIVERSITY WATER SYSTEM (IA5225101)
Perfluoro-4-methoxybutanoic acid (PFMBA)< 3 ng/LNo federal or state limit; shown for transparencyNot detected above the reporting limit2024-01-19 to 2024-10-31UCMR5 Analytical Results: UNIVERSITY WATER SYSTEM (IA5225101)
Perfluorobutanesulfonic acid (PFBS)< 3 ng/L2,000 ng/L EPA health advisory (screening, not a legal limit)Screening level, not a legal limitNot detected above the reporting limit2024-01-19 to 2024-10-31UCMR5 Analytical Results: UNIVERSITY WATER SYSTEM (IA5225101)
Perfluorobutanoic acid (PFBA)< 5 ng/LNo federal or state limit; shown for transparencyNot detected above the reporting limit2024-01-19 to 2024-10-31UCMR5 Analytical Results: UNIVERSITY WATER SYSTEM (IA5225101)
Perfluorodecanoic acid (PFDA)< 3 ng/LNo federal or state limit; shown for transparencyNot detected above the reporting limit2024-01-19 to 2024-10-31UCMR5 Analytical Results: UNIVERSITY WATER SYSTEM (IA5225101)
Perfluorododecanoic acid (PFDoA)< 3 ng/LNo federal or state limit; shown for transparencyNot detected above the reporting limit2024-01-19 to 2024-10-31UCMR5 Analytical Results: UNIVERSITY WATER SYSTEM (IA5225101)
Perfluoroheptanesulfonic acid (PFHpS)< 3 ng/LNo federal or state limit; shown for transparencyNot detected above the reporting limit2024-01-19 to 2024-10-31UCMR5 Analytical Results: UNIVERSITY WATER SYSTEM (IA5225101)
Perfluoroheptanoic acid (PFHpA)< 3 ng/LNo federal or state limit; shown for transparencyNot detected above the reporting limit2024-01-19 to 2024-10-31UCMR5 Analytical Results: UNIVERSITY WATER SYSTEM (IA5225101)
Perfluorohexanesulfonic acid (PFHxS)< 3 ng/L10 ng/L federal MCL (2024)Not detected above the reporting limit2024-01-19 to 2024-10-31UCMR5 Analytical Results: UNIVERSITY WATER SYSTEM (IA5225101)
Perfluorohexanoic acid (PFHxA)< 3 ng/L400,000 ng/L Michigan EGLE state MCL (strictest US state)Not detected above the reporting limit2024-01-19 to 2024-10-31UCMR5 Analytical Results: UNIVERSITY WATER SYSTEM (IA5225101)
Perfluorononanoic acid (PFNA)< 4 ng/L10 ng/L federal MCL (2024)Not detected above the reporting limit2024-01-19 to 2024-10-31UCMR5 Analytical Results: UNIVERSITY WATER SYSTEM (IA5225101)
Perfluorooctanesulfonic acid (PFOS)< 4 ng/L4.0 ng/L federal MCL (2024)Not detected above the reporting limit2024-01-19 to 2024-10-31UCMR5 Analytical Results: UNIVERSITY WATER SYSTEM (IA5225101)
Perfluorooctanoic acid (PFOA)< 4 ng/L4.0 ng/L federal MCL (2024)Not detected above the reporting limit2024-01-19 to 2024-10-31UCMR5 Analytical Results: UNIVERSITY WATER SYSTEM (IA5225101)
Perfluoropentanesulfonic acid (PFPeS)< 4 ng/LNo federal or state limit; shown for transparencyNot detected above the reporting limit2024-01-19 to 2024-10-31UCMR5 Analytical Results: UNIVERSITY WATER SYSTEM (IA5225101)
Perfluoropentanoic acid (PFPeA)< 3 ng/LNo federal or state limit; shown for transparencyNot detected above the reporting limit2024-01-19 to 2024-10-31UCMR5 Analytical Results: UNIVERSITY WATER SYSTEM (IA5225101)
Perfluorotetradecanoic acid (PFTA)< 8 ng/LNo federal or state limit; shown for transparencyNot detected above the reporting limit2024-01-19 to 2024-10-31UCMR5 Analytical Results: UNIVERSITY WATER SYSTEM (IA5225101)
Perfluorotridecanoic acid (PFTrDA)< 7 ng/LNo federal or state limit; shown for transparencyNot detected above the reporting limit2024-01-19 to 2024-10-31UCMR5 Analytical Results: UNIVERSITY WATER SYSTEM (IA5225101)
Perfluoroundecanoic acid (PFUnA)< 2 ng/LNo federal or state limit; shown for transparencyNot detected above the reporting limit2024-01-19 to 2024-10-31UCMR5 Analytical Results: UNIVERSITY WATER SYSTEM (IA5225101)
Not detected (29)
  • 11-Chloroeicosafluoro-3-oxaundecane-1-sulfonic acid (11Cl-PF3OUdS)
  • 1H, 1H, 2H, 2H-perfluorohexane sulfonic acid (4:2 FTS)
  • 1H, 1H, 2H, 2H-perfluorooctane sulfonic acid (6:2 FTS)
  • 1H, 1H, 2H, 2H-perfluorodecane sulfonic acid (8:2 FTS)
  • 9-Chlorohexadecafluoro-3-oxanone-1-sulfonic acid (9Cl-PF3ONS)
  • 4,8-Dioxa-3H-perfluorononanoic acid (ADONA)
  • Hexafluoropropylene oxide dimer acid (HFPO-DA) (GenX chemicals)
  • N-ethyl perfluorooctanesulfonamidoacetic acid (NEtFOSAA)
  • Nonafluoro-3,6-dioxaheptanoic acid (NFDHA)
  • N-methyl perfluorooctanesulfonamidoacetic acid (NMeFOSAA)
  • Perfluorobutanoic acid (PFBA)
  • Perfluorobutanesulfonic acid (PFBS)
  • Perfluorodecanoic acid (PFDA)
  • Perfluorododecanoic acid (PFDoA)
  • Perfluoro (2-ethoxyethane) sulfonic acid (PFEESA)
  • Perfluoroheptanoic acid (PFHpA)
  • Perfluoroheptanesulfonic acid (PFHpS)
  • Perfluorohexanoic acid (PFHxA)
  • Perfluorohexanesulfonic acid (PFHxS)
  • Perfluoro-4-methoxybutanoic acid (PFMBA)
  • Perfluoro-3-methoxypropanoic acid (PFMPA)
  • Perfluorononanoic acid (PFNA)
  • Perfluorooctanoic acid (PFOA)
  • Perfluorooctanesulfonic acid (PFOS)
  • Perfluoropentanoic acid (PFPeA)
  • Perfluoropentanesulfonic acid (PFPeS)
  • Perfluorotetradecanoic acid (PFTA)
  • Perfluorotridecanoic acid (PFTrDA)
  • Perfluoroundecanoic acid (PFUnA)
Commercial · test your own tap

The system record stops at your property line

Screening tells you if something is worth a closer look; a lab result is the number you can act on.

As an Amazon Associate, PurityMap earns from qualifying purchases. Affiliate disclosure

  • Screening: quick check, not lab-grade

    Safe Home DIY Lead in Drinking Water Combo Test Kit

    Safe Home (EnviroTestKits)

    Lead, read as one of three ranges: 0–4, 5–15 or 15+ ppb

    Turnaround: 5 minutes

    What it can't tell you: It shows a lead range, not an exact level, and tests nothing else unless you pay extra for the optional lab test.

Questions

About University Water System

Follow University Water System

Get PurityMap updates about this water system.

Follow this water →
What is the phone number for University Water System?

University Water System's phone number on EPA record is 319-335-5165. Its mailing address is ATTN WATER PLANT MANAGER, JIM ZARUBA, UNIV WATER PLT 208 W BURLINGTON, IOWA CITY, IA 52242.

Where does University Water System get its water?

According to EPA's record, University Water System uses surface water from its own intake.

Does University Water System have any EPA violations?

EPA's record shows 2 health-based violations for University Water System in the 10 years to July 9, 2026. No open health-based violations on EPA record in the last 10 years. The latest legal-limit breach on record was in the period starting April 2017. EPA also lists 4 missed or late tests or reports in 10 years. The record comes from EPA's SDWIS compliance database.

What is University Water System's latest lead result?

Lead was not detected at the 90th percentile of tap samples in University Water System's latest lead and copper round, which ended in December 2024. The federal action level is 15 µg/L.

Who do I contact about my University Water System water bill?

PurityMap has no verified website for University Water System. Its phone number on EPA record is 319-335-5165. Its mailing address on EPA record is ATTN WATER PLANT MANAGER, JIM ZARUBA, UNIV WATER PLT 208 W BURLINGTON, IOWA CITY, IA 52242. Your water bill lists the ways to contact your supplier and pay. PurityMap does not take payments.