Change
Water utility · Concordia Parish · Louisiana

Lake St John Waterworks District 1

No open health-based violations on EPA record in the last 10 years; latest legal-limit breach in the period starting October 2023.

Serves about 2,067 people (689 connections) with groundwater from its own wells.

  • PWSID LA1029006
  • EPA registered name: LAKE ST JOHN WATERWORKS DISTRICT 1
  • EPA record checked June 23, 2026
Contact

Contact Lake St John Waterworks District 1

From EPA's record for LA1029006. PurityMap is independent of Lake St John Waterworks District 1.

Mailing address
LAKE ST JOHN WATERWORKS DISTRICT NO 1, 1185 HWY 569
FERRIDAY, LA 71334
Directions ↗

Are you this utility? Correct this listing →

EPA compliance record

What EPA's record shows

43 health-based violations in the last 10 years, from EPA's SDWIS compliance database.

  • Total trihalomethanes (TTHM), a by-product of disinfecting water with chlorine, were above the legal limit in 8 quarters since October 2019.
  • Haloacetic acids (HAA5), a by-product of disinfecting water with chlorine, were above the legal limit in 16 quarters since July 2019.
Recent health-based violations for Lake St John Waterworks District 1 (PWSID LA1029006)
PeriodContaminantMeasuredLegal limitEPA status
Oct–Dec 2023Total trihalomethanes (TTHM)0.081 mg/L0.080 mg/LResolved
Jul–Sep 2023Haloacetic acids (HAA5)0.062 mg/L0.060 mg/LResolved
Apr–Jun 2023Haloacetic acids (HAA5)65 µg/L0.060 mg/LResolved
Apr–Jun 2023Total trihalomethanes (TTHM)91 µg/L0.080 mg/LResolved
Jan–Mar 2023Total trihalomethanes (TTHM)0.089 mg/L0.080 mg/LResolved
Show all 25
PeriodContaminantMeasuredLegal limitEPA status
Jan–Mar 2023Haloacetic acids (HAA5)0.068 mg/L0.060 mg/LResolved
Oct–Dec 2022Total trihalomethanes (TTHM)0.082 mg/L0.080 mg/LResolved
Oct–Dec 2022Haloacetic acids (HAA5)0.063 mg/L0.060 mg/LResolved
Jul–Sep 2022Total trihalomethanes (TTHM)0.083 mg/L0.080 mg/LResolved
Apr–Jun 2022Haloacetic acids (HAA5)0.066 mg/L0.060 mg/LResolved
Jan–Mar 2022Haloacetic acids (HAA5)0.067 mg/L0.060 mg/LResolved
Oct–Dec 2021Haloacetic acids (HAA5)0.068 mg/L0.060 mg/LResolved
From September 2021Groundwater Rule––Resolved
Jul–Sep 2021Haloacetic acids (HAA5)0.068 mg/L0.060 mg/LResolved
Apr–Jun 2021Haloacetic acids (HAA5)0.071 mg/L0.060 mg/LResolved
Apr–Jun 2021Total trihalomethanes (TTHM)0.081 mg/L0.080 mg/LResolved
Jan–Mar 2021Haloacetic acids (HAA5)0.069 mg/L0.060 mg/LResolved
Oct–Dec 2020Haloacetic acids (HAA5)0.069 mg/L0.060 mg/LResolved
Jul–Sep 2020Haloacetic acids (HAA5)0.074 mg/L0.060 mg/LResolved
Apr–Jun 2020Haloacetic acids (HAA5)0.069 mg/L0.060 mg/LResolved
Jan–Mar 2020Total trihalomethanes (TTHM)0.081 mg/L0.080 mg/LResolved
Jan–Mar 2020Haloacetic acids (HAA5)0.07 mg/L0.060 mg/LResolved
Oct–Dec 2019Total trihalomethanes (TTHM)0.082 mg/L0.080 mg/LResolved
Oct–Dec 2019Haloacetic acids (HAA5)0.072 mg/L0.060 mg/LResolved
Jul–Sep 2019Haloacetic acids (HAA5)0.062 mg/L0.060 mg/LResolved
  • Lead: the 90th-percentile result in the latest lead and copper round (the round ending December 31, 2024) was not detected. The federal action level is 15 µg/L, a trigger for more treatment steps, not a legal limit.
  • Missed or late tests or reports: 3 in 10 years.
  • EPA lists 111 enforcement actions in 10 years; the latest on January 16, 2025.

No lab results for other contaminants (like PFAS) are on file for this system. EPA required that testing from systems serving more than 3,300 people, plus a sample of smaller ones.

Commercial · test your own tap

The system record stops at your property line

Screening tells you if something is worth a closer look; a lab result is the number you can act on.

As an Amazon Associate, PurityMap earns from qualifying purchases. Affiliate disclosure

  • Screening: quick check, not lab-grade

    Safe Home DIY Lead in Drinking Water Combo Test Kit

    Safe Home (EnviroTestKits)

    Lead, read as one of three ranges: 0–4, 5–15 or 15+ ppb

    Turnaround: 5 minutes

    What it can't tell you: It shows a lead range, not an exact level, and tests nothing else unless you pay extra for the optional lab test.

Questions

About Lake St John Waterworks District 1

Follow Lake St John Waterworks District 1

Get PurityMap updates about this water system.

Follow this water →
What is the phone number for Lake St John Waterworks District 1?

Lake St John Waterworks District 1's phone number on EPA record is 318-757-3853. Its mailing address is LAKE ST JOHN WATERWORKS DISTRICT NO 1, 1185 HWY 569, FERRIDAY, LA 71334.

Where does Lake St John Waterworks District 1 get its water?

According to EPA's record, Lake St John Waterworks District 1 uses groundwater from its own wells.

Does Lake St John Waterworks District 1 have any EPA violations?

EPA's record shows 43 health-based violations for Lake St John Waterworks District 1 in the 10 years to July 9, 2026. No open health-based violations on EPA record in the last 10 years. The latest legal-limit breach on record was in the period starting October 2023. EPA also lists 3 missed or late tests or reports in 10 years. The record comes from EPA's SDWIS compliance database.

What is Lake St John Waterworks District 1's latest lead result?

Lead was not detected at the 90th percentile of tap samples in Lake St John Waterworks District 1's latest lead and copper round, which ended in December 2024. The federal action level is 15 µg/L.

Who do I contact about my Lake St John Waterworks District 1 water bill?

PurityMap has no verified website for Lake St John Waterworks District 1. Its phone number on EPA record is 318-757-3853. Its mailing address on EPA record is LAKE ST JOHN WATERWORKS DISTRICT NO 1, 1185 HWY 569, FERRIDAY, LA 71334. Your water bill lists the ways to contact your supplier and pay. PurityMap does not take payments.